man mge-shut (Administration système) - Driver for MGE UPS serial SHUT Protocol UPS equipment
NAME
mgeshut - Driver for MGE UPS serial SHUT Protocol UPS equipment
NOTE
This man page only documents the hardwarespecific features of the mgeshut driver. For information about the core driver, see nutupsdrv(8).
SUPPORTED HARDWARE
mgeshut support all recent MGE UPS models which use the SHUT (Serial HID UPS Transfer) protocol at 2400 bps. Supported models are:
Pulsar Ellipse S, Pulsar Ellipse USBS Pulsar Ellipse Premium S, Pulsar Ellipse Premium USBS Pulsar EXtreme C, Pulsar Esprit, Pulsar Evolution, NOVA AVR (Serial), Galaxy 3000 / PW (with RS232 HID COM ports card, ref 66066).
Older models, such as Pulsar ESV+, Pulsar EX and Pulsar ES+, use the UTalk protocol and should use the mgeutalk driver.
EXTRA ARGUMENTS
This driver supports the following optional settings in the ups.conf(5):
- lowbatt=num
- Set the low battery warning threshold at which shutdown is initiated by upsmon(8). The factory default value is 30 (in percentage), and only be settable depending on the exact model.
- offdelay=num
- Set the timer before the UPS is turned off after the kill power command is sent (via the -k switch). The default value is 20 (in seconds), and MUST BE LOWER than ondelay.
- ondelay=num
- Set the timer for the UPS to switch on in case the power returns after the kill power command had been sent but before the actual switch off. This ensures the machines connected to the UPS are, in all cases, rebooted after a power failure. The default value is 3 (in 10 seconds units, which means 30 seconds), and MUST BE GREATER than offdelay.
- notification=num
- Set notification type to 1 (no), 2 (light) or 3 (yes). The default value is 3 (yes) because of some early Ellipse models which need it.
KNOWN ISSUES
Pulsar Ellipse S: Repetitive stale status Loss of communication
Several users have reported "data stale" errors with Pulsar Ellipse equipment. This lasts around 10 seconds and happens once every few hours. This is due to the fact that the SHUT protocol is verbose, and the driver sometimes does not handle all of it during the usual polling interval in upsd. To solve this problem, change the value of MAXAGE to 25 in upsd.conf. Also add "notification=3" in ups.conf (thanks to Julien Lesaint and Fabien).
AUTHOR
Arnaud Quette <arnaud.quette@free.fr> or <arnaud.quette@mgeups.com>
Philippe Marzouk <philm@users.sourceforge.net>