man tripplite (Administration système) - Driver for TrippLite SmartPro UPS equipment
NAME
tripplite - Driver for TrippLite SmartPro UPS equipment
NOTE
This man page only documents the hardwarespecific features of the tripplite driver. For information about the core driver, see nutupsdrv(8).
SUPPORTED HARDWARE
This driver should work on the SmartPro line, including the SMART700 and SMART700SER. It only supports SmartPro models that communicate using the serial port.
EXTRA ARGUMENTS
This driver supports the following optional settings in the ups.conf(5):
- offdelay=num
- Time to wait before the UPS is turned off after the kill power command is sent. The default value is 64 (in seconds).
- rebootdelay=num
- Set the timer before the UPS is cycled after the reboot command is sent. The default value is 64 (in seconds).
- startdelay=num
- Set the time that the UPS waits before it turns itself back on after a reboot command. The default value is 60 (in seconds).
KNOWN ISSUES AND BUGS
Battery charge information may not be correct for all UPSes. It is tuned to be correct for a SMART700SER. Other models may not provide correct information. Information from the manufacturer would be helpful.
AUTHORS
Rickard E. (Rik) Faith <faith@alephnull.com> Nicholas Kain <nicholas@kain.us>