NAME
apcupsd - daemon for most APC's UPS for Linux
SYNOPSIS
/sbin/apcupsd
/etc/apcupsd/apccontrol
/etc/apcupsd/apcupsd.conf
/sbin/apcaccess
/sbin/apcnetd
DESCRIPTION
This document is considerably out of date. It can be used for a brief overview of apcupsd, but you should consult the html manual for current information. Normally this manual will be loaded on your system in the doc directory, which varies from system to system. Otherwise, you may find an online version at: http://www.apcupsd.com
This daemon can be used for controlling the most APC UPSes. During a power failure, "apcupsd" will inform the users about the power failure and that a shutdown may occur. If power is not restored, a system shutdown will follow when the battery is exausted, a timeout (seconds) expires, or runtime expires based on internal UPS calculations determined by power consumption rates. If the power is restored before one of the above shutdown conditions is met, apcupsd will inform users about this fact.
The shutdown is made by script calls to "/etc/apcupsd/apccontrol", which is called by "apcupsd". Consequently, no changes to /etc/inittab are necessary. There is no communication between apcupsd and init(1) process. Apcupsd modifies the halt script so that at the end of the shutdown process, apcupsd will be re-executed in order to power off the UPS. On certain platforms (e.g. FreeBSD) there is no halt script so apccontrol must be modified to cause apcupsd to power off the UPS after a delay time.
The apcupsd daemon now supports two networking modes that function independently, but if desired they can both run at the same time.
Most users will probably enable the first network mode and simplest (NIS or Network Information Service), which permits apcupsd to serve status and event information to clients over the network.
The second networking mode is for multiple networked machines that are powered by the same UPS. In this mode, one machine is configured as a master with the UPS attached to the serial port. The other machines (max. 20) powered by the same UPS are configured as slaves. The master has a network connection with the slaves and sends them information about the UPS status. This mode is significantly more complicated to setup than the NIS networking mode described above.
For details and configurations on these networking modes please see the manual.
RedHat and SuSE versions of Linux have direct install support. All other flavors of Linux may need some fussing with to get the install correct.
OPTIONS
- -c --configure
- Attempts to configure the UPS EPROM to the values specified in the configuration file "/etc/apcupsd/apcupsd.conf". This option is now deprecated (not supported) and should not be used. Instead use the apctest program, which has an interactive EEPROM configuration.
- -d --debug <level>
- Turns on debugging output.
- -f --config-file <file>
- Specifies the location of the configuration file. The default is: /etc/apcupsd/apcupsd.conf
- -k --killpower
- Attempt to turn the UPS off. This option is normally only used by the daemon itself to shut the UPS off after a system shutdown has completed.
- -V --version
- Prints the apcupsd version number and the help.
- -? --help
- Prints a brief apcupsd help screen.
CONFIGURATION
It may be necessary to change the configuration information in the file "/etc/apcupsd/apcupsd.conf" to meet your needs and to correspond to your configuration. This file is a plain ASCII file and you can use your favorite editor to change it.
Configuration commands in /etc/apcupsd/apcupsd.conf are:
GENERAL CONFIGURATION COMMANDS
UPSCABLE
-- <type of cable you are using>
[ simple | 940-0020B | 940-0023A (broken) ]
[ smart | 940-0024B | 940-0024C ]
[ 940-0095A | 940-0095C ]
[ ether ]
[ usb ]
UPSTYPE
-- <Type of APCC UPS you have>
[ dumb | apcsmart | net | usb | snmp | test ]
DEVICE
-- <name of serial port>
Please specify which device is used for UPS communication.
The default is /dev/ttyS[0|1|2|3]. If you have a USB UPS,
you should leve the DEVICE directive blank and apcupsd
will figure out where your device is located. If you have
problems, please see the manual as it has more details.
LOCKFILE
-- <path to lockfile>
By supplying this argument, "apcupsd" tries to create a lockfile
for the serial or USB port in the specified directory.
CONFIGURATION COMMANDS USED BY THE NETWORK INFORMATION SERVER
NETSTATUS
[on | off]
This configuration command turns the network information server
on or off. If it is on, apcupsd will spawn a child process that
serves STATUS and EVENTS information over the network. This
information is currently used by the Web based CGI programs.
The default is on. In some cases, for added security, you may
want to invoke a separate information server daemon from the inetd
daemon. In this case, NETSTATUS should be off.
STATUSPORT
<port>
This configuration command specifies the port to be used by the
apcupsd server. The default is 3551.
EVENTFILE
<filename>
If you want the apcupsd network information server to provide
the last 10 events via the network, you must specify a
file where apcupsd will save these events. The default is:
/var/log/apcupsd.events. Currently, apcupsd will save
at most the last 50 events. When more than 50 events are
recorded and a network request for the events arrives,
the network server will truncate the file to
the most recent 10 events. Consequently this file
will not grow indefinitely as long as the events are
checked from time to time.
CONFIGURATION COMMANDS USED TO CONTROL SYSTEM LOGGING
STATTIME
STATFILE
DATATIME
FACILITY
CONFIGUATION COMMANDS USED DURING POWER FAILURES
ANNOY
-- <time in seconds>
Please specify the time in seconds between messages requesting
logged in users to get off the system. This timer starts only when
the UPS is running on batteries. The default is 300 seconds
(5 minutes).
ANNOYDELAY
-- <time in seconds>
Please specify delay time in seconds before apcupsd begins requesting
logged in users to get off the system. This timer starts
only after the UPS is running on batteries.
This timer is reset when the power returns. The default
is 60 seconds. That is the first warning to log off the
system occurs after 60 seconds on batteries.
NOLOGON
-- <specifies when apcupsd should create the nologon file>
[ disable | timeout | percent | minutes | always ] are valid types.
Based on Ten (10) percent of a setting. This allows one to define the point when the /etc/nologin file is added. This is important for allowing systems with BIG UPSes to run as normally until the system administrator determines the need for dumping users. The feature also allows the system administrator to hold the "ANNOY" factor until the /etc/nologin file is added.
disable prevents apcupsd from creating the nologin file.
timeout specifies a specific wait time before creating the nologin file.
percent specifies the percent battery charge remaining before creating the nologin file.
minutes specifies the battery runtime remaining before creating the nologin file.
always causes the nologin file to be immediately created on a power failure.
BATTERYLEVEL
-- <percent of battery>
If BATTERYLEVEL is specified, during a power failure, apcupsd will
shutdown the system when the remaining battery charge falls below the
specified percentage. The default is 5.
MINUTES
-- <battery runtime in minutes>
If MINUTES is specified, during a power failure, apcupsd will
shutdown the system when the remaining remaining runtime on batteries
as internally calculated by the UPS
falls below the time specified. The default is 3.
TIMEOUT
-- <time in seconds>
After a power failure, the system will be shutdown after TIMEOUT seconds
have expired. Normally for SMARTUPSes, this should be zero so that the
shutdown time will be determined by the battery level or remaining runtime
(see above). This command is useful for dumb UPSes that do not report
battery level or the remaining runtime. It is also useful for
testing apcupsd in that you can force a rapid shutdown by setting
a small value (e.g. 60) and pulling the plug to the UPS.
The timeout for the master is always 30 seconds longer than slaves.
TIMEOUT, BATTERYLEVEL, and MINUTES can be set together without problems. The daemon will react to the first case or test that is valid. Normally SmartUPS users will set TIMEOUT to zero so that the system is shutdown depending on the percentage battery charge remaining (BATTERYLEVEL) or the remaining battery runtime (MINUTES).
CONFIGURATION COMMANDS FOR SHARING A UPS
UPSCLASS
-- <class of operation>
[ standalone | shareslave | sharemaster ] and
[ netslave | netmaster ] are valid types.
[ standalone | netslave | netmaster ] are tested classes.
[ shareslave | sharemaster ] classes are being tested.
The default is "standalone" and should be used for all machines powered by the UPS and having a serial port connection to the UPS, but where there are no other computers dependent power from the same UPS. This is the "normal" case.
Use "netmaster", if and only if you have a serial port connection to the UPS and there are other machines deriving power from the same UPS.
Use "netslave" if and only if you have no serial port connection to the UPS, but you derive power from it.
Use "shareslave" if and only if you are using a ShareUPS and connected to a BASIC Port with Simple Signal.
Use "sharemaster", if and only if you are using a ShareUPS and connected to the ADVANCED Port Smart Signal control.
UPSMODE --
[ disable | share | net | sharenet ] are valid types.
[ disable | net ] are the only known and tested classes.
[ share | sharenet ] classes are being tested.
BETA [ share ] For two or seven (2/7) additional simple signal ports on a SmartAccessories(tm) (internal/external box) for SmartUPSes.
NETTIME
-- <time in seconds>
The rate in seconds that broadcasts information to Slave machines.
This rate is reset if there is a power state change. This value
is now passed to the slaves to sync. the openning of a socket
by the slave for the master.
NETPORT
-- <TCP|UDP port number>
This unix service port number must be set in the /etc/services file
as follows:
tab tab(spacejunk) tab tab
name (stuff)/xxp #
apcupsd NETPORT/tcp #
apcupsd NETPORT/udp #
MASTER
-- <name of master> for Slave machine.
The name of the master which is authorized to send commands to this slave.
SLAVE
-- <name of slave(s)> for Master machine.
The name of the slave machine attached to the master.
There can be max. 20 slaves attached to one master.
USERMAGIC
-- < user defined password> for the slave machine.
The second level of password security. It must be (17) characters long
without spaces. This is passed to the master machine during
initialization of sockets. This string should be different for
each and every slave on the network. This is not at all secure as
passwords are passed in the clear. Please protect your network by
firewalling or tcpwrappers.
SMARTUPS
If you start getting the follow message:
Emergency -- Batteries Have Failed!
Change Them NOW!
Act upon it quickly. It means what it says.
Also, not all "SmartUPS" models are eqaully smart. A non-NET or old class of "SmartUPS" has a subset of the full UPSlink(TM) language, and can not be polled for its control codes.
SHAREUPS
Special note for ShareUPS users, TIMEOUT, BATTERYLEVEL, and MINUTES are disabled or set to default values. Currently, there is not a known way for early signals to be sent to BASIC Ports. MINUTES are set to 0.
FILES
/etc/apcupsd/apcupsd.conf
- configuration file.
/var/log/apcupsd.status
- STATUS file
/var/log/apcupsd.events
- where up to the last 50 events are stored
for the network information server.
EVENTS
apcupsd generates events when certain conditions occur such as a power failure, batteries exhausted, power return,
These events are sent to the system log, optionally sent to the temporary events file (/var/log/apcupsd.events), and they also generate a call to /etc/apcupsd/apccontrol which in turn will call any scripts you have placed in the /etc/apcupsd directory.
DATA format
If the DATATIME configuration command is set nonzero, apcupsd will log a data record at the interval defined on the DATATIME command. This data record is in a format similar to the PowerChute data file format.
STATUS format
The STATUS output is in ASCII format and generally there is a single piece of information on each line output. The format varies based on the type of UPS that you are using.
DATE : time and date of last update
CABLE : cable type used
UPSMODEL : ups type or signal method
UPSMODE : tells apcupsd what to check
SHARE : if ShareUPS is used, this determines what
SmartUPS and MatrixUPS Smart Signals
ULINE : Current (observed) Input Line Voltage
MLINE : Max (observed) Input Line Voltage
NLINE : Min (observed) Input Line Voltage
FLINE : Line Freq (cycles)
VOUTP : UPS Output Voltage
LOUTP : Percent Load of UPS Capacity
BOUTP : Current Charge Voltage of Batteries
BCHAR : Batteries Current Charge Percent of Capacity
BFAIL : UNSIGNED INT CODE (ups state)
UTEMP : Current UPS Temp. in Degrees Cel.
DIPSW : Current DIP switch settings for UPS.
Newer BackUPS Pro Smart Signals
ULINE : Current (observed) Input Line Voltage
MLINE : Max (observed) Input Line Voltage
NLINE : Min (observed) Input Line Voltage
FLINE : Line Freq (cycles)
VOUTP : UPS Output Voltage
LOUTP : Percent Load of UPS Capacity
BOUTP : Current Charge Voltage of Batteries
BCHAR : Batteries Current Charge Percent of Capacity
BFAIL : UNSIGNED INT CODE (ups state)
BackUPS Pro and SmartUPS v/s Smart Signals
LINEFAIL : OnlineStatus
BATTSTAT : BatteryStatus
MAINS : LineVoltageState
LASTEVNT : LastEventObserved
BackUPS and NetUPS Simple Signals
LINEFAIL : OnlineStatus
BATTSTAT : BatteryStatus
BackUPS Pro and SmartUPS v/s Smart Signals
OnlineStatus BatteryStatus LineVoltageState
LastEventObserved
BackUPS and NetUPS Simple Signals
OnlineStatus BatteryStatus
SEE ALSO
The html manual installed on your system or http://www.apcupsd.com